# Pleated Panel Pre Filter

> Source (HTML): https://www.whalesens.com/products/pleated-panel-filter.html
> Last updated: 2026-09-20 16:13:23

The first filtration stage in most air handling units: a pleated pad that keeps dust off everything behind it.

A pleated panel filter is the first filtration stage in most air handling units. The media is folded into pleats rather than laid flat, which fits a large filter area into a shallow frame, and it is the cheapest way to keep dust off everything behind it. In practice it is judged on holding capacity and on how long it stays in the unit, not on efficiency alone.

The pleats are held open by the frame and by hot-melt beads rather than by the media itself, which is what keeps the filter from collapsing under load. Grades follow EN779 and cover the usual pre-filter duties, and the standard depths are not interchangeable in practice — each suits a different slot and a different budget. The washable version is a service decision as much as a cost one: media, frame and mesh separate cleanly, but it only pays for itself where the dust is the kind that rinses out.

## Key features

- **Pleated media area**: Up to 3x a flat pad (The same frame takes far more media, which is where the low resistance comes from)
- **Low initial resistance**: 30–40 Pa (Rated across 2,800–3,400 m³/h depending on depth and grade)
- **Washable and reusable**: Detachable media (Media, frame and protective mesh separate for cleaning and can be rebuilt)
- **Rigid frame**: No sagging at 96 mm (Galvanised steel, aluminium or stainless steel keeps pleats spaced in service)
- **Standard face sizes**: 595 x 595 mm (20, 46 and 96 mm depths fit common AHU holding frames without adapters)
- **Three grades, one frame**: G2 / G3 / G4 (Upgrade arrestance later without changing the frame or the duct)
- **Moisture resistant**: 100% RH (Continuous service to 100 °C with 120 °C instant peaks)
- **Colour-coded media**: Grade at a glance (Maintenance staff identify the grade on site without reading a label)

## Specifications

- Filtration grade: G2, G3, G4 (EN779); EU2, EU3, EU4 (EUROVENT)
- Media: Polyester synthetic fibre, pleated
- Frame options: Aluminium, galvanised steel, stainless steel
- Standard face size: 595 x 595 mm
- Depths: 20, 46, 96 mm
- Initial resistance: 30 – 40 Pa
- Final resistance: 200 – 250 Pa
- Rated airflow: 2,800 – 3,400 m³/h
- Filtration efficiency: 75%, 85%, 95% (ASHRAE 52.1-1992)
- Target particles: ≥ 5 μm coarse dust and foreign particles
- Continuous temperature: ≤ 100 °C
- Instant temperature: ≤ 120 °C
- Moisture resistance: 100% RH
- Maintenance: Washable, detachable media and protective mesh

## Applications

Office Buildings, Conference Rooms, Hospitals, Shopping Malls, Schools, Museums, Airports, Cleanroom Pre-filtration

## Technical Index


## Material characteristics


## Technical Parameter