# HVAC Air Filter Media

> Source (HTML): https://www.whalesens.com/products/hvac-air-filter-media.html
> Last updated: 2026-09-20 16:13:23

Coarse-stage air filter media for HVAC and ventilation intakes, trapping large dust particles before they reach coils, fans and ductwork.

HVAC air filter media is a coarse-stage material fitted at the intake of ventilation and air-conditioning equipment, ahead of the finer filters in the system. It removes the bulk of large particles, dust and dirt before they reach coils, fans and ductwork in general ventilation and industrial pre-filtration. It is supplied as cut slices, framed slices or full rolls, so it can be used as a replaceable pad in a holding frame or fed into equipment that forms its own filter.

The media is a polyester fibre web combed into dense layers and bonded by hot air fusion, with the air outlet face covered by mesh and reinforced with cloth so the sheet keeps its shape and passes air evenly. A viscosity treatment holds captured dust in the media rather than letting it shake loose downstream. Dust holding capacity and the pressure drop the media adds decide how often the pad is changed and how much fan energy the system spends; a washable construction extends service life where the dust is not oily or sticky. Flame-retardant grades are available where the ductwork requires them.

## Key features

- **Three grades**: G2 / G3 / G4 (150, 200 and 250 g/m² rolls cover coarse pre-filtration duty)
- **Dust holding capacity**: 450 – 580 g/m² (Gradient density traps dust through the depth, not just on the face)
- **Low resistance**: 20 – 25 Pa initial (Measured at the grade's own test face velocity)
- **Washable**: Reusable media (Synthetic fibre holds up to washing and re-fitting)
- **Flame retardant**: F1 (DIN53438), B1 (Rated for ventilation and air-conditioning intakes)
- **Roll or cut**: 1 m and 2 m rolls (Slices, framed slices or whole rolls from the same media)

## Specifications

- Filtration grade: G2, G3, G4
- Thickness: 10, 15, 20 mm
- Weight: 150, 200, 250 g/m²
- Average weight efficiency: 83%, 85%, 91%
- Test face velocity: 2 / 1.5 / 1 m/s for G2 / G3 / G4
- Dust holding capacity: 450, 500, 580 g/m²
- Initial resistance: 20 – 25 Pa
- Final resistance: 200 – 250 Pa
- Media: Synthetic fibers
- High temperature resistance: ≤100 °C
- Instant temperature resistance: ≤120 °C
- Moisture resistance: 100% RH
- Flame retardant level: F1 (DIN53438), B1 (GB/T 17591-2006)
- Filter object: ≥ 5 μm particles

## Applications

HVAC Systems, Industrial Pre-filtration

## Technical Index


## Material characteristics


## Technical Parameter


## Verified facts (with sources)

- **Filtration grade**: G2, G3, G4 — [source](https://www.whalesens.com/products/hvac-air-filter-media.html)
- **Filter media**: Synthetic fibers — [source](https://www.whalesens.com/products/hvac-air-filter-media.html)